VF(R)-12 Wbudowany wysokonapięciowy próżniowy przełącznik obciążenia AC

VFR-12R AC Vacuum Load Switch is a new generation of high voltage vacuum switching equipment, developed specifically to meet market demand and modern design concepts. It is mainly used in indoor armored air-insulated switchgear and is capable of stable operation within the specified voltage range under normal conditions.

Overview of VF(R)-12

VF(R)-12 is a kind of indoor embedded high voltage AC vacuum load switch-fuse combination device. It is suitable for various power grids and operates safely and stably within its technical parameters. With advanced design, this device is widely used in modern power systems.

Standard produktu

VF(R)-12 Vacuum load switch conforms to the following standards:

GB 3804-2004: High-voltage load AC switches with rated voltage between 3.6 kV and 40.5 kV.
GB 16926-2009: Standard for high-voltage load AC switch-fuse combinations.

Parametry techniczne

   Pozycja Jednostka Wartość odniesienia
VF-12/T630-20
Vacuum load
switch
VFR-12/T125-50
Vacuum load
switch-fuse
combination
VFH-12/T630-25
High breaking
capacity vacuum
switch
VFHR-12/T125-50
High breaking
capacity vacuum
switch-tuse
combination
   Rated yoltage kV 12 12 12 12
napięcie wytrzymywane impulsu błyskawicy kV 75 75 75 75
    Rated insulation level 1min power-frequency withstand voltage kV 42 42 42 42
   Rated frecuency Hz 50/60 50/60 50/60 50/60
   Prąd znamionowy A 630 125(fuse) 630 125(fuse)
   Znamionowy prąd zwarciowy kA 50(fuse 25(are suppreson chamber) 25im pcesson harx
   Znamionowy prąd zwarciowy (wartość szczytowa) kA 50 63
   Znamionowy krótkotrwały prąd wytrzymywany kA 20 25
   Znamionowy prąd wytrzymywany (wartość szczytowa) kA 50 63
   Rated breaking current of cable during charge A 16
   Rated breaking current of no-load transformer kVA 1250 1250
   Rated breaking take-over current A 3150 3150
   Breaking times of the rated short-circuit current Czasy
   Żywotność mechaniczna Poziom M2 M2 leve M2 leve Poziom M2
   Waga kg 125

Operating conditions

Ambient temperature: -40°C to +40°C (less than 35°C within 24 hours)
Relative humidity: ≤95% (daily average), or ≤90% (monthly average)
Wysokość: ≤1000 metrów

Transformer and fuse selection

Fuses have the ability to cut off high currents in less than 10 milliseconds and have a breaking capacity of up to 50KA, which makes them effective in protecting transformers. When selecting fuses, it is important to consider that the fuse current needs to be 1.6 times its rated value to cope with potential inrush currents. The designer should also allow a margin for the fuse, taking into account the fluctuations in the grid. If the fuse is to be used for high voltage motor protection, consideration should also be given to the frequency of motor start-ups, as frequent start-ups may result in the fuse not being able to cool down in time and thus failing.

Fuse Selection

Napięcie pierwotne
transformator (kV)
Pojemność
the transformer(kVA)
Model bezpiecznika Prąd znamionowy
of the fuse(A
Model dla rynku krajowego Model dla rynku międzynarodowego
6.6 200 XRNT-10 12kV BDGHC 31.5
250 40
300/315 50
400 12kV BDGHC 63
500 80
630 90

Wymiary całkowite i instalacyjne

Całkowity wymiar wewnętrznego wyłącznika próżniowego wysokiego napięcia prądu przemiennego VF(R)-12 (na kółkach)

AC Vacuum Load Switch
Szerokość obudowy (mm) P(mm) A(mm) B(mm) C(mm) E(mm) φW(mm)
650 150 500 530 490 203 35
800 210 650 680 640 278 35
1000 275 850 880 840 378 35