Home » Product » Vacuum Circuit Breaker » ZN85-40.5 High Voltage Vacuum Circuit Breaker

ZN85-40.5 High Voltage Vacuum Circuit Breaker

ZN85-40.5 is a kind of high-voltage vacuum circuit breaker for indoor use, which is suitable for AC 50Hz and 35kV power system. It is mainly used for protection and control equipment in power plants, substations and other places.

Description

ZN85 is a high voltage vacuum circuit breaker with frequency of 50Hz and rated voltage of 40.5kV. It is very suitable for use in industrial and mining enterprises, power plants and substations where frequent operation is required. Its stable performance and easy installation make it an ideal choice for control and protection in high-voltage transmission and distribution systems.

Product standard

ZN85-40.5 high voltage vacuum circuit breaker complies with the following standards:

IEC 62271-100 High voltage AC circuit breaker
GB/T 11022-2011 Standard General Specification for High Voltage Switchgear and Controlgear
GB 1984 High voltage AC circuit breaker
GB 311.1 Insulation coordination of high-voltage power transmission and distribution equipment

Working conditions

Normal operating conditions:
Ambient temperature: -40℃ to +40℃ (temperature below 35℃ within 24 hours)
Relative humidity: ≤95% (daily average) or ≤90% (monthly average)
Altitude: ≤1000 meters

Technical Parameters

1.1 Technical parameters

Item                                                                                   Unit Reference value
    Rated yoltag kV 40.5
Lightning impulse withstand voltage kV 185
    Rated insulation level            1min power-frequency withstand voltage kV 95
    Rated frequeng, Hz 50/60
    Rated current A 630/1250/1600/2000/2500/3150
    Rated short-circuit breaking current kA 20/25/31.5
    Rated short-circuic making current (peak value kA 506,380
    Rated short-time withstand current kA 20/25/31.5
    Rated withstand current (peak value kA 506,380
    Required operation sequence 0-0.3s-CO-180s-CO
    Rated short-circuit duratio 5 4
    Times of making-breaking with the rated short-circuit curren Time 30
    Mechanical life M2 level
    Weigh kg 350

1.2 Mechanical Parameters

  ltem Unit Reference value
  Gap of contacts mm 20±2
   Contact overtravel mm 6±1
  Average making speed m/s 0.6±0.2
  Average breaking speed m/s 1.5~2.0
  Bounce time in contact making ms ≤3
  Non-synchronous making/breaking of contact ms ≤2
  Resistance of the circuit of each phase μ Q ≤80
  Permissible total wear thickness of the moving/fixed contact mm 3

Overall And Installation Dimension

Overall dimension of ZN85-40.5(insulating cylinder handcart)indoor high-voltage alternating-current circuit breaker

voltage-vacuum-circuit-breaker
   Rated current(A) 630 1250 1600 2000     2500
   Rated breaking current(kA) 202,531.5 202,531.5 2,531.5 31.5     31.5
   Fixed contact size D(mm) φ35 φ49 中55 φ79     φ109
   Interphase distance(mm) 300±1.5
   Handcart travel(mm) 610±2